A-A-50735
Other publications. The following document forms a part of this CID to the extent specified herein. Unless otherwise specified, the issue of the documents which are DOD adopted shall be those listed in the issue of the DODISS specified in the solicitation. Unless otherwise specified, the issues of documents not listed in the DODISS shall be the issue of the nongovernment documents which is current on the date of the solicitation.
AMERICAN NATIONAL STANDARDS INSTITUTE
ANSI-C62.41-1980, 2.5KY), Category A
(Application for copies of ANSI publications should be addressed to the American National Standards Institute, 1430 Broadway, New York, NY 10018.)
Order of precedence. In the event of a conflict between the text of this CID and the references cited herein (except for associated detail specifications, specification sheets or MS standards) the text of this CID shall take precedence. Nothing in this CID, however, shall supersede applicable laws and regulations unless a specific exemption has been obtained.
Salient characteristics. The equipment shall be capable of operation within the accuracies, limits, and specifications herein.
1. Safety. The equipment shall be UL (Underwriters Laboratories) listed and approved and/or shall comply with the type III safety requirements of the latest MIL-T-28800.
a. Leakage current protection. Protection shall be provided from leakage current in excess of 5 milliamperes (ma) rms (AC and DC) from any accessible conductive parts of equipment (including control shafts with knobs broken or removed and recessed calibration or adjustment controls) to either pole of the power source for any position of the power switch(es).
b. Radio frequency interface (RFI) capacitors. Any capacitor used in RFI filters shall be rated for at least four (4) times the operating voltage.
c. Type III ventilation openings.
(1) Ventilation openings shall be designed to prevent accidental contact with live electrical circuits3 and mechanical moving parts.
(2) Top ventilation openings shall incorporate small mesh, screening or similar design to prevent expulsion of hot electronic particles due to failure of electronic devices such as capacitors.
2. Parts, materials, and processes. Except for marking, the meter shall comply with the type III parts, materials, and process requirements of MIL-T-28800. Nonstandard parts approval requests shall be in accordance with the latest MIL-T-28800. Front panel marking shall be in accordance with the latest MIL-T-28800.
For Parts Inquires submit RFQ to Parts Hangar, Inc.
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business